Leaflets - Installation & Maintenance Guides - Drawings
For more detailed information - please visit our Download Information page
Specifically designed for infrequent emptying by suction tanker.
This range is specifically designed for infrequent emptying by suction tanker. It is most suited to sites with a high flow rate such as food processing factories, hospitals, prisons etc.
These very high quality separators have been tested to the rigorous EN 1825 test in which a mixture of oil and water is passed through the separator for a minimum 20 minute test period and then samples of the outflow are taken and examined by infra-red spectrophotometry to determine exactly how many parts of oil is in each million parts of water.
The Lamina Filtertrap achieved better than the 25 parts per million required under EN 1825.
We achieve these excellent results with the following features:-
For more detailed information - please visit our Download Information page
Model | Part No. | Meals/Day | Nettt Cap. (litres) | Length Along Pipe Run | Width Across Pipes | Inlet Invert |
---|---|---|---|---|---|---|
NS10TE | 9107 | 1000 | 2000 | 2400 | 1500 | 550 |
NS15TE | 9108 | 1500 | 3000 | 2400 | 1500 | 550 |
NS20TE | 9109 | 2000 | 4000 | 2400 | 1500 | 550 |
NS25TE | 9110 | 2500 | 4000 | 2400 | 1500 | 550 |